Technical
Effective operating time 20 hours (normal usage)
Temperature limits Line fluid (at the sensor): +2 to +50 °C
AC6-SP+ (Standard)
Measurement range 0.5 kPa to 250 kPa
Measurement accuracy - Differential pressure
Range 0.5-10 kPa Accuracy +/-0.1 kPa
Range 10-250 kPa Accuracy +/-1.0% reading
Hysteresis 0.2% span
Maximum Total System Pressure 10 bar
AC6-HP+ (High pressure)
Measurement range 1.0 kPa to 800 kPa
Measurement accuracy - Differential pressure
Range 1.0-20 kPa Accuracy +/-0.2 kPa
Range 20-800 kPa Accuracy +/-1.0% reading
Hysteresis 0.2% span
Maximum Total System Pressure 20 bar
The Sales kits come as standard with x2 angled 2.0 mm diameter Binder connectors and x2 angled 3.3 mm diameter Binder connectors. Additional fittings are available - see accessories.
It should be noted that the angle pattern connectors are recommended for all 'difficult to access' measurement locations.
Wherever possible the manufacturer programmes into the instrument the Kv characteristics of most common valves in the market. Currently this is over 6,000 individual valve types from 80 manufacturers, but some manufacturers such as TA Hydronics will not release data relating to some of their new products. If your application requires use in these instances please check with our technical team to check product suitability.