Directly descended from the original SPC Pro it combines all the qualities that made that product a market leader with a host of enhanced features. All designed to help you get the job done better, quicker and easier. Based on the well-proven "3 currents, 1 voltage" hook-up, the only voltage connection it needs is a standard 13A socket. For surveys where mains power is not available the unit's internal battery provides up to two weeks no voltage logging, increasing as much as 12 weeks with the external battery pack option. Current measurement is via fully isolated flexible hoop type CT's which makes the SPC Pro 2 data logger incredibly safe to use. The unit is also very easy to set up and connect and requires no detailed knowledge of electrical systems from the operator.

Features

The SPC Pro 2 is easy to hook-up - no prior set-up is required unless the data storage rate needs changing, so normally it's a case of clipping on the flexible hoop type CT's, plugging in the power lead and pressing the start button.

Download is equally easy - plug in a USB stick and press the download button, or connect the unit to your PC's USB port with the lead provided. Either way our PowerPackPro software will find the logger or the USB stick automatically and guide you through a fool proof sequence to ensure that accurate results for voltage, current, power factor, kilowatts kilowatt hours and kVArh are configured for immediate viewing.

The instrument uses a completely secure and non-volatile flash memory and has its own back-up for its on-board clock.

The powerful internal battery allows it to be used as a 'current only' logger for up to two weeks where a mains supply is not available.

The SPCPro2 is a professional-grade instrument for the measurement and logging of three-phase and single phase electrical loads. It is able to measure the following parameters:

  • Voltage amplitude x 1
  • Current amplitude x 3
  • Current phase angle* x 3       *Referenced to the measured voltage
  • From the above data, the following parameters are presented:  V, I, PF, kW, kWh, kVArh, cost and CO2 emissions (kg) via the instrument’s dedicated software package ‘PowerPackPro’.

Technical

  • Non-invasive
  • Safe hook-up
  • Battery backup
  • 2 to 2000A range CT's

Kit Contents:

  • SPC Pro 2 unit c/w 3 x flex 2000A CT's
  • USB download cable
  • Mains power lead
  • PowerPackPro software
  • Zip holdall

NOTE: Any data stored in logger memory is erased when a new survey is started. The USB Stick memory WILL NOT be erased when a new survey is started.  

PowerPackPro software is also available to download online: https://spcloggers.com/downloads/ 

Elcomponents SPC Pro hire kit | Energy analyser
Elcomponents SPC Pro hire kit | Energy analyser
Elcomponents SPC Pro c/w 3 x flex 2 to 2000 A CTs, USB download cable mains lead, PowerPackPro software and case

Support documents

  • Download
  • Category
  • File type
  • Download
Download
Elcomponents SPC Pro 2 data sheet.pdf Elcomponents SPC Pro 2 data sheet
Category
Technical document
File type
Adobe Acrobat
Download (2 MB)
Download
Elcomponents SPC Pro 2 user manual.pdf Elcomponents SPC Pro 2 user manual
Category
Technical document
File type
Adobe Acrobat
Download (2 MB)

Common customer questions & answers

QQuestion Can the SPC Pro 2 be used for multiple data logs?
AAnswer In normal use, the unit will record for the first logging period you do. Thereafter, any further logging that is carried out will overwrite the original data (the unit doesn't store multiple data logging files). Either download the unit between each logging session/location, or plug in a USB stick and proceed to log the data to the USB.