The Testo 175T series of data loggers are small and portable which makes them the ideal device for monitoring temperatures in the modern workplace. Typical applications include the commissioning of buildings, the validation of temperature cold rooms and the monitoring of freezer temperatures. Logger size 82mm (H) x 52mm (W) x 30mm (D).

Features

General logger hire information

All hire data loggers are set as a default to record at 5-minute intervals with a user manual start on site by pressing and holding GO for 4-5 seconds. If an alternative logging interval or a timed start is required, then we must be notified of this prior to the despatch of the hire instruments.

For the hire of 1-9 units we do not charge for the time to download the instruments when they are returned to our Bracknell offices and will supply the data in Excel spread sheet format via email. For the hire of 10 or more units the costs for the data download is charged at an hourly rate. If downloaded data is required in a graphical format additional charges are also applied based on specific client requirements.

The 175T3 instruments have adjustable logging intervals via the software from 10 seconds to 24 hour increments, with a 16,000 sized readings memory. This for example equates to:-

16000 size memory (2 channels)

30 second logging interval = 2.8 days maximum capacity

1 minute logging interval = 5.6 days maximum capacity

5 minute logging interval = 27.8 days maximum capacity

10 minute logging interval = 55.6 days maximum capacity

NOTES: If x1 channel is switched off the above periods can be doubled.

All probes and extension leads for use with the 175T3 product are charged for at an additional cost.

Technical

175T3 specification (2 channel temperature logger with external connections for Type T or Type K sensors)

Storage temperature -40 to +85°C

Operating temperature 0 to +85°C

Memory 16 000 readings

Probe input Type T

Measuring range -50 to +400 °C

Accuracy ±0.5 °C (-50 to +70 °C) ±0.7 % of mv (+70.1 to +1000 °C)

Resolution 0.1 °C

Probe input Type K

Measuring range -50 to +1000 °C

Accuracy ±0.5 °C (-50 to +70 °C) ±0.7 % of mv (+70.1 to +1000 °C)

Resolution 0.1 °C

Testo 175T1 | Temperature data logger hire
Testo 175T1 | Temperature data logger hire
Available to hire is the Testo 175T1,1 channel temperature logger with internal (NTC) sensor. All units are supplied with a 3 point ISO traceable calibration certificate.

Support documents

  • Download
  • Category
  • File type
  • Download
Download
Testo 171 175 177 hire user manual.pdf Testo 171 175 177 hire user manual
Category
Technical document
File type
Adobe Acrobat
Download (69 KB)
Download
Testo 175 series user manual.pdf Testo 175 series user manual
Category
Technical document
File type
Adobe Acrobat
Download (824 KB)
Download
Testo ComSoft Basic V5.0 software (for logger types 174, 175, 176 and 177) - SP6.4.exe Testo ComSoft Basic V5.0 software (for logger types 174, 175, 176 and 177) - SP6.4
Category
Software
File type
Windows software
Download (168 MB)
Download
Testo ComSoft Basic V5.0 software manual .pdf Testo ComSoft Basic V5.0 software manual
Category
Technical document
File type
Adobe Acrobat
Download (1 MB)

Common customer questions & answers

QQuestion Can I manually stop and/or restart the logger to take measurements in a different location?
AAnswer No, once the instrument has started logging, you can only stop by connecting to a PC with the correct interface and software.
QQuestion What is the default logging interval period?
AAnswer All instrument rental models are supplied as standard with the logging interval set at 5 minutes from user starting logging by holding Go for 3-4 seconds. If an alternative interval time or a a start and end time / date is required, please specify this at the time of ordering. You cannot set the units without software and a PC.
QQuestion How do I start the loggers and know that they are recording?
AAnswer Press [GO] for approx. 4 seconds to start the logger measurement program.
The measurement program starts, and the 'Await' status changes to 'Rec' in the display to advise that the unit is now recording.