The Wohler DP 700 is an easy to use positive and negative pressure high accuracy air leakage tester which can be used in a wide range of applications. Not only can the instrument be used for the airtightness of duct systems it can also be used for testing enclosures such as air handling units, climatic chambers, vehicles, and electrical cabinets.
The DP 700 has been especially designed for leakage tests according to EN 12599 - Test procedures and measurement methods to hand over air conditioning, and ventilation systems according to EN 14134 - Performance testing and installation checks of residential ventilation systems. The air tightness values are to the classes of EN 13779 (identical to EN 12237, 1507, 15727, 13403, 1751 and 13180).
Features
- The ideal tool for the QA testing of ducts including systems such as those built into residential dwellings
- Additional adapters for air flow rates < 0.3 l/s with a high level of measurement accuracy.
- Suitable for leakage tests of AHU's
- Easy to operate
- Store up to 100 measurements
- Automatic or manual measurement modes
- Practical size, 2 easy to carry storage cases
Important notes
The Wöhler DP 700 is not designed for continuous use or for long / extended periods in an attempt to locate leaks within a system.
The Wohler DC series software is not available to purchase or as an optional accessory.
The Instrument Solutions rental models are supplied with 110 V and 230 V power leads.
Technical
Power supply 110 V or 230 V
Range (230 V unit) 0 to 55.00 l/s
Class A Class B Class C Class D
20 Pa 290 m² 870 m² 2600 m² 7800 m²
200 Pa 65 m² 195 m² 580 m² 1750 m²
2000 Pa 15 m² 44 m² 130 m² 390 m²
Theoretical duct surface area testing limits at maximum allowable leakage rates (230 V 50 Hz unit)
Range (110 V unit) 0 to 40.00 l/s
Resolution 0.0001 l/s to 0.3000 l/s 0.001 l/s to 3.000 l/s 0.01 l/s > 3.00 l/s
Accuracy (flow measurement) ± 0.0009 l/s or ± 5 % of the test value whichever is higher
Pressure range ± 7000 Pa
Pressure resolution 0.1 Pa to ± 900 Pa, then 1 Pa
Pressure accuracy ± 0.5 Pa or ± 2.5 % of the test value whichever is greater
Current consumption 9 A maximum
Weight (without accessories) 9.5 kg