Chauvin Arnoux PEL 103 | Energy alayser

Contact Instrument Solutions

The Chauvin Arnoux PEL 103 is a single or three phase power and energy logger which can monitor systems with or without a neutral, as well as other complex configurations. It comes with a backlit display, a magnetic case to make installation easy within narrow distribution cabinets, compact designed flexible CT's which fit on any type of switchboard without preventing the cabinet door from closing, and it can be fitted (with suitable precautions) to live systems using the magnetized voltage probes. Furthermore, in addition to the instruments display real time data the live information can be viewed using Bluetooth and the PEL andriod App.

Features

  • Voltage up to 1,000 V
  • Current up to 10,000 A
  • Voltage ratio / current ratio up to 650,000 V / up to 25,000 A
  • Power from 10 W/var/VA to 10 GW/Gvar/GVA
  • Energy up to 4EWh / 4 EVAh / 4 Evarh
  • Phase: cos φ, tan Φ, PF
  • Harmonics up to 50th order
  • 2 GB SD memory card (SD-HC card up to 32 GB)

Technical

Installation types      Single-phase, split-phase, three-phase with or without neutral and many other specific configurations

Accuracy class       0.2 %

Number of channels       3 voltage inputs / 3 current inputs (calculation of neutral current)

Network frequency       DC, 50 Hz, 60 Hz and 400 Hz

Voltage range       0 to 1,000 V AC and DC

CT clamp versions 

Type                            Range

MN93                          2 to 240 AAC

MN93A                        0.005 AAC to 5 AAC / 0.1 AAC to 120 AAC

C193                            3 A to 1,200 AAC

A193 and MA193       100 mA to 10,000 AAC *

PAC93                          10 A to 1,000 AAC / 10 A to 1,400 ADC

E3N                              50 mA to 10 AAC/DC - 100 mA to 100 AAC/DC

* MA193 MiniFlex clamps are supplied as standard with the PEL 103 kits and are suitable for cables up to 70 mm diameter.

Voltage ratio/ current ratio       Up to 650,000 V / up to 25,000 A

Calculated measurements      Power 10 W to 10 GW / 10 var to 10 Gvar / 10 VA to 10 GVA

Energy      Up to 4EWh / 4 EVAh / 4 Evarh

Phase        cos φ, tan Φ, PF

Harmonics        Up to the 50th order

Complementary functions       Phase order and Min / Max

Sampling / acquisition rate / aggregation      28 samples/period - 1 measurement per second from 1 min to 60 min

Memory SD card       2 GB (SD-HC up to 32 GB)

Communication       Bluetooth (Class 1), Ethernet, USB

Power supply         110 V - 250 V (+ 10 %, - 15 %) @ 50-60 Hz & 400 Hz

Safety        IEC 61010 CAT IV 600 V and CAT III 1,000 V

Demonstration video

Chauvin Arnoux PEL 100 range product overview

Support documents

  • Download
  • Category
  • File type
  • Download
Download
Chauvin Arnoux - The Streamlined Energy Carbon Reporting Scheme - SERC - fact sheet.pdf Chauvin Arnoux - The Streamlined Energy Carbon Reporting Scheme - SERC - fact sheet
Category
Technical document
File type
Adobe Acrobat
Download (489 KB)
Download
Chauvin Arnoux clamp range data sheet.pdf Chauvin Arnoux clamp range data sheet
Category
Technical document
File type
Adobe Acrobat
Download (1 MB)
Download
Chauvin Arnoux MiniFlex MA193 clamp data sheet.pdf Chauvin Arnoux MiniFlex MA193 clamp data sheet
Category
Technical document
File type
Adobe Acrobat
Download (814 KB)
Download
Chauvin Arnoux NF A5 power module data sheet.pdf Chauvin Arnoux NF A5 power module data sheet
Category
Technical document
File type
Adobe Acrobat
Download (668 KB)
Download
Chauvin Arnoux PEL 103 power and energy logger quick start guide.pdf Chauvin Arnoux PEL 103 power and energy logger quick start guide
Category
Technical document
File type
Adobe Acrobat
Download (1 MB)
Download
Chauvin Arnoux PEL 103 power and energy logger user manual.pdf Chauvin Arnoux PEL 103 power and energy logger user manual
Category
Technical document
File type
Adobe Acrobat
Download (8 MB)
Download
Chauvin Arnoux power and energy logging fact sheet.pdf Chauvin Arnoux power and energy logging fact sheet
Category
Technical document
File type
Adobe Acrobat
Download (351 KB)

Common customer questions & answers

QQuestion How do you know the status of the memory of the PEL 103 device?
AAnswer In "Configure Device" under "Recording", there is the status of the SD card. This include information regarding the % used of the card and the total memory of the card.
QQuestion Is it possible to download a measurement data while another programme (campaign) is in progress?
AAnswer Yes at any time it is possible to retrieve a measurement campaign either during this campaign or other in memory.