DP Measurements TT550 Series | Micromanometer

Contact BSRIA Instrumentation

The TT550 series are a range of high resolution (0.01 Pa) programmable digital micromanometers which are available with dry cell or rechargeable batteries. Rental kits come with and without a 305 mm Pitot tube.

The DP Measurements TT550 series of high resolution micromanometers come with a unique differential capacitance transducers and programmable auto zero facility. Each can store up to three Pitot tube factors, up to four duct settings and a maximum of 2500 readings. Models available include dry cell and rechargeable options.

Features

Auto ranging Automatically changes scale and resolution depending upon the pressure being applied. Ensuring accurate readings at all times. Maximum pressure range 5.0 kPa.

Over range  If the applied pressure is greater than the calibration limit. Display will indicate - - - - - - - -, to protect the instrument from being damaged.

Data logging Up to 2500 readings can be stored either manually or automatically with date and time stamp. Data can be viewed on display with averaging function, which can be downloaded to a PC via the RS 232 output socket using the optional software.

Display  For easy viewing, the main digits are 10 mm high, unit of measurement, fast or slow mode, when the auto zero is in operation, number memory location used and with back light.

Audible feedback      Can be heard when a key is pressed thus giving that extra confidence.

Multiple ranges      Select the unit of measurement via the range key.

Auto switch off      For a longer battery life.

Auto zero     No need to disconnect the instrument from the pressure source to zero.

Technical

Pressure range      ± 0.06 to 99.99 Pa, ± 100.0 to 999.9 Pa, ± 1000 to 5000 Pa

Velocity range      Elliposoidal 2.00 to 90.0 m/sec, dpm-i 0.27 to 30.0 m/sec, dpm Ane 0.27 to 25.0 m/sec

Accuracy        Please see manufacturers datasheet

Operational temperature     0 to 50 oC

Span stability versus temperature      0.1 % of range in use per oC

Zero drift        Negligible due to auto zero system, when auto zero set to 60 second intervals (2 minute warm up)

Zero system accuracy       ± 0.05 Pascal typical

Orientation effect      (any 45o change) 0.1 Pascal typical

Output socket      RS 232 (baud rate 9600)

Data logging      Up to 2500

Software         Download data to PC in basic form

Power source      Dry cell (MN1604, PP3) or rechargeable

System air leak       0.1 ml/minute at 5 KPa (typical)

Safe line / differential pressure     15 KPa

Storage temperature limits      - 5 to + 50 oC

Weight        555 g with battery

Dimensions     45 mm x 92 mm x 185 mm

Support documents

  • Download
  • Category
  • File type
  • Download
Download
DP Measurements TT550 series data sheet.pdf DP Measurements TT550 series data sheet
Category
Technical document
File type
Adobe Acrobat
Download (216 KB)
Download
DP Measurements TT550 series user manual.pdf DP Measurements TT550 series user manual
Category
Technical document
File type
Adobe Acrobat
Download (420 KB)