The TT570 series of hand held digital micromanometers are compact lightweight bi-directional units, with excellent stability and resolution. The very wide range of applications include:
• HVAC Commissioning and maintenance
• Aerodynamics and air flow research
• COSHH requirements relating to air flow and pressure
• Paint booth and clean room pressure differential measurement
Wide range of models available in metric and imperial measurement units with dry cell or rechargeable options.
Features
Auto ranging Automatically changes scale and resolution depending upon the pressure being applied. Ensuring accurate readings at all times. Maximum pressure range ± 7.5k Pa.
Over range If the applied pressure is greater than the calibration limit. Display will indicate - - - - - - - -, to protect the instrument from being damaged.
Data logging Up to 2500 readings can be stored either manually or automatically with date and time stamp. Data can be viewed on display with averaging function, which can be downloaded to a PC via the basic optional software.
Display For easy viewing, the main digits are 10 mm high, unit of measurement, fast or slow mode, when the auto zero is in operation, number memory location used and with back light.
Audible feedback Can be heard when a key is pressed thus giving that extra confidence.
Multiple ranges Select the unit of measurement via the range key.
Auto switch off For a longer battery life.
Auto zero No need to disconnect the instrument from the pressure source to zero.
Technical
Pressure, velocity and accuracy Please see manufacturers datasheet as this varies per model
Operational temperature 0 to 50 oC
Span stability versus temperature 0.1 % of range in use per oC
Zero drift Negligible due to auto zero system, when auto zero set to 60 second intervals (2 minute warm up)
Zero system accuracy ± 0.05 Pascal typical
Orientation effect (any 45o change) 0.1 Pascal typical
Output socket RS 232 (baud rate 9600)
Data logging Up to 2500 points
Software Download data to PC in basic form
Power source Dry cell (MN1604, PP3) or rechargeable
System air leak 0.1 ml/minute at 5 kPa (typical)
Safe line / differential pressure 15 kPa
Storage temperature limits - 5 to + 50 oC
Weight 555 g with battery
Dimensions 45 mm x 92 mm x 185 mm